Aithon PV33 has been tested to European Standards 13501-1 and EN 13501-2 Reaction to Fire. The system can achieve a Euroclass B-s1 d0 rating on timber and wood derivatives with a minimum thickness of 10mm and a density equal to or greater than 390kg/m³.
Spreading rate of Aithon PV33 = 25m² per 7.5kg and 67m² per 20kg for Euroclass B
This product can be applied in either 1 or 2 coats at the above spreading rates.
It requires the AITHON F3 Finish coat on all projects to ensure that the intumescent does not turn milky over time.
Not suitable for use on all woods. Please contact us for more details.
Application & storage conditions:
Temperatures should be between 5°C – 30 °C when the product is applied
Temperatures should remain above 5°c during drying
Ambient humidity should not exceed 70%
Storage temperature: 5°C – 30°C
Storage & Application Conditions:
Storage temperature must be between 5°C and 30°C.
Please ensure that the product is applied and dried in conditions that are warmer than 5°C and that ambient humidity is lower than 70%.
The moisture content of the timber should be checked and must be below 12% before application.
The F3 Finish coat can be applied one day after applying the PV33 basecoat.
Application Instructions
FOR FULL INSTRUCTIONS PLEASE ENQUIRE ON 01752 690997 OR [email protected]
PV33 and the F3 Finish can be applied by brush, roller or a spray gun.
Aithon PV33 is supplied as a gel product. It can be spray applied as it is or thinned with 5% water. Brush or roller application requires a 10% to 20% thinning with water.
Aithon F3 may be used as it is or thinned with white spirit. Usually 10% thinning is sufficient.
CANNOT BE PURCHASED ONLINE. PLEASE ORDER ON 01752 690997 or [email protected]
IMPORTANT INFORMATION ON PURCHASING OF PASSIVE FIRE PROTECTION PRODUCTS NOTICE:
The information displayed about the products on this website is to be used for guidance ONLY, we advise that all customer contact our technical department to obtain a free no obligation specification and quotation before purchasing goods directly from the website.
Products purchased directly from our website without specification will NOT qualify for certification.
Please be aware that any negligence caused by failure to obtain the relevant advice, or availment of our specification and estimation service, will absolve International Passive Fire Ltd from any liability should Passive Fire Protection Products prepared, or used, by the purchaser, or any other parties, result in damage to property or human life, or for any monetary costs incurred due to incorrect usage.